Both are planned gaps between building sections, and in everyday conversation the names get mixed up. The difference is how much movement they are designed for, and how fast it happens.
Expansion joint
- Handles slow, daily and seasonal movement from heat, shrinkage and settlement
- Typical gap: 25 – 100 mm
- Typical movement: ±7.5 to ±15 mm
Seismic joint
- Separates building blocks so each one can sway independently during an earthquake
- Typical gap: 100 – 500 mm, depending on building height and seismic zone
- Movement in every direction, often ±25 to ±30 mm or more, and sudden
- Common on hospitals, medical colleges and other critical public buildings
Why the cover design changes
A seismic joint cover has to move in every direction without jamming or tearing out its anchors. That’s why our seismic systems use a self-centring arrangement: circular sphere ends lock into an aluminium extrusion and can rotate and slide freely. After the shaking stops, the centre plate settles back into position.
On the Government Medical College & Hospital at Bhojpur, for example, the 500 mm gaps used our FFS 150 floor-to-floor and WWS 500 wall-to-wall systems. Both are made from Hindalco aluminium with a 1–1.2 mm EPDM membrane underneath.
Checklist for specifying a seismic joint
- Get the design gap and the expected movement in X, Y and Z from the structural engineer
- Check the load: pedestrian, hospital trolley or vehicle
- Confirm the floor finish and its thickness so the cover sits flush
- Insist on a continuous moisture barrier
- Ask for shop drawings showing fixing centres (typically 300–400 mm)
Need help choosing a joint for your project? Send us the joint width and location or call +91 98187 49056. We usually reply with a recommendation the same day.